The intelligent measurement and control device for transformers is a temperature controller specially designed for dry-type transformers. The characteristics of this device are strong anti-interference ability, Большая выходная контактная способность, Полный набор функций, colorful LCD display interface with illustrations, Простая настройка, и простота в эксплуатации; With reliable EMC, EMI performance. The temperature sensor can be customized and uses conventional PT100 temperature measurement. The intelligent temperature measurement device for dry-type transformers is installed on the ground. Этот продукт обладает уникальными техническими преимуществами при измерении температуры в особых средах, таких как высокое напряжение и сильные электромагнитные помехи.
① The device has a maximum of 8 PT100 temperature measurement channels and a maximum of 2 PTC trip protection channels. Can be configured as needed.
② 1 RS485 communication channel, MODBUS RTU protocol.
③ 1-way fan control, default contact capacity 5A/250VAC, optional high power. The fan operation can be manually controlled by touching the buttons.
④ 1 door switch signal input.
⑤ 8-way relay output, can be used for door opening alarm output, over temperature alarm output, over temperature trip output, device fault alarm output, iron core alarm output, power loss alarm output, fan remote transmission output, fan fault output, output dry contact, contact capacity 5A/AC250V (optional 5A/DC220V). The specific configuration is based on the actual order and wiring diagram.
Особенности продукта
① The protection level is IP4x
② The contact output capacity is large.
③ Equipped with a 5-inch color LCD touch screen display.
④ The Регулятор температуры uses an ARM architecture CPU with strong data processing capabilities and stable system performance.
⑤ The circuit board design concept of the temperature controller is modular design, с сильным и слабым электрическим разделением для предотвращения пространственных перекрестных помех.
⑥ The temperature controller contains a clock chip and historical data storage with time markers.
⑦ RS485 communication function, communication protocol is the international open standard protocol Modbus RTU.
Dimensions of intelligent temperature measurement devices for special transformers
Способ установки:Floor standing
Размеры внешнего вида:1500mmx600mmx400mmm (height x width x depth)
Bottom installation size: 300mm x 400mm (Расстояние между отверстиями) (installation holes 4x diameter 14)
Installation dimension diagram of XB-S201 special transformer intelligent temperature measurement device