Neach-dèanamh de Sensor Teòthachd Fibre Optic, Siostam sgrùdaidh teòthachd, Proifeiseanta OEM/ODM Factaraidh, Slàn-reicear, Supplier.customized.

Post-d: fjinnonet@gmail.com |

Rianadair Teòthachd Transformer Seòrsa tioram/Rianadair Teòthachd/

Dry type transformer temperature controller BWDK-S3206

Temperature range:-30.0℃~240.0℃

Ambient temperature:-20ºC~+55ºC

Ambient humidity:<95% (25ºC)

Working voltage:AC 220V (+10%,-15%)

Working frequency rate :50Hz OR 60Hz(±2Hz)

Measurement accuracy :±1%FS(Thermostat level 0.5,Sensor class B)

Resolution ratio :0.1ºC

Fan output total capacity :5A/250VAC

Control output capacity :5A/250VAC;5A/30VDC(resistivity)

Power dissipation:≤8W

Production standards:JB/T7631-2005 Electronic temperature controller for Transformers”Industry standards

Adoption of accreditation standards:ISO9001:2008 International Quality Management System Certification

Pass the test standard:IEC61000-4:1995 International standard
GB/T17626-2008 Electromagnetic compatibility test and measurement techniques”standard

  • Product Details

The temperature controller for Electric power dry-type transformers is an intelligent controller designed specifically for the safe operation of Electric power cruth-atharraichean. The temperature controller adopts microcontroller technology and uses the platinum thermistor embedded in the Electric power transformer winding to detect and display the temperature rise of the Electric power transformer winding. It can automatically start and stop the cooling fan to force air cooling of the winding, avoiding or reducing faults caused by high temperature in the Electric power transformer. It can also control the output of over temperature alarm and over temperature trip to ensure that the transformer operates in a safe state, thereby extending the working life of the Electric power transformer.

Product Selection:

model function
BWDK-S3206D
  1. Monitor up to three dry-type transformer windings;
  2. Display maximum temperature;
  3. Built-in fan control, fan exerciser;
  4. Alarming function and relay output control;
  5. Trip function and relay output control;
  6. Automatic fault detection function;
  7. Historical record function;
  8. Range in temperature revise;
  9. Self-inspection;
  10. Switch input judging function.
BWDK-S3206E 4-20mA output for integration with SCADA systems
BWDK-S3206F RS485 or RS232 serial communication function.
BWDK-S3206G An additional sensor is added to measure the ambient temperature
BWDK-S3206I An additional sensor is added to measure the temperature of silicon steel sheet