Der Hersteller von Faseroptischer Temperatursensor, Temperatur-Überwachungssystem, Professionell OEM/ODM Fabrik, Großhändler, Lieferant.customized.

E-Mail: fjinnonet@gmail.com |

Blogs

What is the safest temperature measurement method for dry-type transformer windings

Overview of solutions for fluorescent fiber optic temperature controllers for dry-type transformers
The measurement range specified in the “Elektronischer Temperaturregler für Transformatoren” (JB/T7631-2016), which uses Pt100 as the traditional temperature sensor, kann nur auf unter 1000V begrenzt werden, and this sensor is made of metal material, which poses a safety hazard. Deshalb, temperature sensor probes and leads for measuring transformer winding temperature have higher requirements.

The fiber optic temperature controller uses our company’s independently developed fluoreszierender faseroptischer Temperatursensor as the temperature sensing element. Dieses Temperaturmesselement ist immun gegen elektromagnetische Störungen und resistent gegen Hochspannung (100KV/Glasfaser-zu-Erde-Leitungsabstand von 0,4 m). Fluorescent fiber optic temperature measurement completely solves potential safety hazards from the source of temperature measurement and improves the safety level of transformers.

Target of fluoreszierendes faseroptisches Temperaturmesssystem für Trockentransformatoren
For the operating environment of dry-type transformers, Die Isolierung und Abschirmung von externen elektrischen Störsignalen wird von der Stromversorgung aus erreicht, Ende des Signaleingangs, Ende des Signalausgangs, und Temperierkastengehäuse.
No metallic substances, Eigensicherheit.
Als Reaktion auf Vibrationen, Staub, moisture, oil and other on-site working environments, multi-layer protective measures are taken to ensure that the fiber optic Temperaturregler has good electromagnetic compatibility, ensuring stable and reliable operation.
Design principles of fluorescent fiber optic temperature measurement host for dry-type transformers
Prinzip der Praktikabilität
Der Systemaufbau folgt dem Prinzip der Praxistauglichkeit. Auf der Grundlage der Praktikabilität, Fortschrittlichkeit und Weitsicht werden berücksichtigt, und Standard, Fortschrittliche und ausgereifte Produkte und Entwicklungsplattformen werden ausgewählt, um ein System aufzubauen, das praktisch ist und praktische Probleme löst.

Prinzip der Normung
Die Systemsoftware- und -hardwareplattformen sowie die Anwendungsentwicklungswerkzeuge, die bei der Anwendungsentwicklung verwendet werden, sollten den nationalen Normen entsprechen, Standards des Ministeriums für Informationsindustrie, relevante technische Spezifikationen und Anforderungen des Unternehmens.

Das Prinzip der Uniformität
Befolgung der Politik des zentralisierten Informationsmanagements, Gesamtplanung, Gesamtausführung, und schrittweise Umsetzung, Der Implementierungsprozess verkörpert vier einheitliche Prinzipien: Einheitliche Führung, Einheitliche Planung, Einheitliche Standards, und einheitliche Organisation und Umsetzung.

Prinzip der Zuverlässigkeit
The software and hardware resources need to ensure the uninterrupted and reliable operation of the faseroptisches Temperaturmesssystem for 7 × 24 Stunden. Deshalb, Es ist notwendig, ein vollständiges Design von Zuverlässigkeitsmaßnahmen zu erstellen, um den hochzuverlässigen Betrieb des Systems zu gewährleisten und die Zuverlässigkeitsanforderungen der wichtigsten Systemanwendungen vollständig zu berücksichtigen.

Zuverlässiger Sicherheitsmechanismus
Dieses System verwendet eine Reihe von sicheren Verschlüsselungsmaßnahmen, mit eingebautem 64 Bit-Verschlüsselungsalgorithmus. Das System verfügt über eine höhere Sicherheit und kann Datenlecks und -diebstahl effektiv verhindern, Gewährleistung der Sicherheit, Genauigkeit, und Integrität der Systemdaten, und Verhinderung illegaler Tätigkeiten von Betreibern und illegalen Tätigkeiten rechtmäßiger Betreiber.

Die Bedienoberfläche ist einfach, freundlich, und hochintelligent
Das System prüft automatisch die Rechtmäßigkeit der eingegebenen Daten und gibt freundliche Eingabeaufforderungen für Bedienungsfehler.

Stabiler Betrieb und zuverlässige Daten.
Die Plattform ist einfach zu bedienen, Einfach zu meistern, und der Installationsprozess ist einfach. Die Daten können bei Bedarf automatisch in verschiedenen Berichten generiert werden, Verbesserung der Managementeffizienz.
Prinzip der fluoreszierenden faseroptischen Temperaturmessung
Die faseroptische Sonde besteht aus drei Teilen: ST-Steckverbinder, Glasfaserkabel, und Endtemperaturmessung Ende. Der ST-Steckverbinder ist das Verbindungsteil mit der Lichtschranke; Glasfaserkabel ist der Übertragungsteil, mit Quarzfaser im Inneren. Die Quarzfaser hat auf der Außenseite eine Beschichtung und eine Ummantelung, und eine Teflon-Schutzhülle am äußersten Teil; The end temperature sensing end contains temperature sensitive rare earth materials, which excite fluorescence after being irradiated by fixed wavelength light. After the excitation stops, the relationship between the decay time constant of fluorescence afterglow and temperature is a quasi exponential function. The temperature can be obtained by measuring the time constant of afterglow; Die optische Faser ist beständig gegen hohe Temperaturen von 200 °C und hat einen Außendurchmesser von 3mm. Langfristiger Biegeradius von 13,2 cm. Short term bending radius 4.4cm

The sensor probe material is rare earth fluorescent material, and its biggest advantage compared to other optical fiber temperature measurement principles is that temperature measurement is independent of light intensity. It has strong compatibility with the inconsistency of fluorescence intensity, optical path attenuation, and circuit drift in hardware. Deshalb, it is not affected by electromagnetic interference and can withstand high voltage, making it very suitable for high voltage, strong magnetic field, flammable and explosive temperature measurement occasions.

Introduction to wiring and installation of fiber optic temperature controllers for dry-type transformers
1.1 Statischer Rahmen
Das System besteht aus drei Teilen: ein fluoreszierender faseroptischer Temperaturregler, eine fluoreszierende faseroptische Sonde, und Glasfaser-Kommunikationssoftware.

Die Datenübertragung zwischen dem Backend-System und dem Temperaturmessterminal erfolgt über die RS485-Kommunikationsmethode.

Alle Datenerfassungen, Management, und Temperaturanzeige werden durch eine Kommunikationssoftware vervollständigt, und das System realisiert hauptsächlich die Datenerfassung und Überwachung der Temperaturmessung. Das faseroptische Temperaturmessterminal integriert mehrkanalige fluoreszierende optische Fasern, Bereitstellung einer externen RS485-Kommunikation, Anti-Interferenz, und korrosionsbeständige Ausführung.

Application functions of fiber optic temperature controller system for dry-type transformers
1.1 Echtzeit-Überwachung
Die Datenerfassungsdichte kann nach Kundenwunsch eingestellt werden, und das System sammelt regelmäßig Daten auf der Grundlage der eingestellten Parameter. Dann, Es wird in Tabellenform oder Kurvenzeichnung angezeigt, um eine Echtzeitüberwachung zu erreichen. Echtzeitüberwachung des Betriebsstatus der Anlage; Echtzeitüberwachung und Aufzeichnung der Reaktortemperatur.

1.2 Basic functions
1) Abfrage von Temperaturdaten

1. Sie können Temperaturdaten für bestimmte Daten abfragen, blättern, drucken, und Export nach Excel.

2) Speicherung historischer Temperaturdaten

1. Permanente Aufzeichnung von Temperaturdaten

Introduction to fiber optic temperature controller for dry-type transformers
2.1 Main features
The fiber optic temperature controller is embedded installation. Dieses Produkt hat einzigartige technische Vorteile bei der Temperaturmessung in speziellen Umgebungen, wie z. B. Hochspannung, starke elektromagnetische Störungen, etc. The temperature hotspot and measurement signal receiving part of the fluorescent faseroptischer Temperatursensor Verwenden Sie keine elektrischen Anschlüsse, die lange Zeit mit hoher Präzision und Stabilität arbeiten können, Deutliche Verbesserung des Anwendungsbereichs. Der faseroptische Temperaturregler hat eine hohe Genauigkeit und Empfindlichkeit, ist resistent gegen hohen Druck und kann fernüberwacht werden, hat eine lange Lebensdauer, ist klein, macht die Gerätewartung einfach und bequem, und sorgt für einen sicheren Transport.

2.2 Hauptfunktionen
Bietet Temperaturmessung mit drei Wicklungen; Automatische/manuelle Start-Stopp-Funktion des Lüfters; Digitale Kompensationsfunktion für die Anzeige der Werte jedes Kanals
The digital tube displays the temperature of the transformer’s hot spot on a circuit;
Black-Box-Funktion bereitstellen, , die Temperaturdaten und historische Höchsttemperaturen vor drei Stromausfällen aufzeichnen kann;
Bieten Sie eine Alarmfunktion für die Öffnung des Transformatortürschranks;
Provide functions such as over temperature alarm, fault alarm, trip, etc
Bietet RS485-Kommunikationsfunktion, Die Kommunikation mit der Zeitmarke kann Timing oder MODBUS-RTU-Protokoll empfangen (F-Funktion)
2.3 Zusätzliche Funktionen
Versorgen 4 unabhängige analoge Stromausgangsfunktionen von 4-20 mA; (E-Funktion)
PTC nichtlineare Widerstandsmessung, Temperaturmessung, Schutzfunktion; (C-Funktion)
Alarmfunktion für die Anstiegsrate der Wicklungstemperatur und der Temperatur des Eisenkerns;
Das Kommunikationsprotokoll kann Methoden wie Profibus annehmen, IEC60870-5-103, Ethernet-Kommunikation, etc;

Faseroptischer Temperatursensor, Intelligentes Überwachungssystem, Verteilter Glasfaserhersteller in China

Fluoreszierende faseroptische Temperaturmessung Fluoreszierendes faseroptisches Temperaturmessgerät Verteiltes faseroptisches Fluoreszenz-Temperaturmesssystem

Anfrage

Zurück:

Nächster:

Hinterlassen Sie eine Nachricht